Hardware Manual for the PCD2.M5 Series│Document 26/856; Version EN 12│2014-07-24
Saia-Burgess Controls AG
Analogue output modules, electrically isolated
Input/output (I/O) modules
6-76
6
Typicaloutputrange(withoutcomponenttolerances):
W605: -0.26V…+10.36V(insteadof0…+10V)
W615: -0mA…+21.4mA(insteadof0…+20mA)
W625: -10.62V…10.36V(insteadof-10…+10V)
Thisrangeisbrokendownona10bitscale(1024steps),asbefore.Theresultisthe
following LSB resolution:
W605: 1 LSB = 10.38 µV
W615: 1 LSB = 21.7 µA
W625: 1 LSB = 20.75 µV
Withthisbalancethenominalrange(0...10V)isnowscaled0...1023,makingit
possible for the output value not to change on an increase of 1 LSB.
IntheFBstheoutputvaluesarenotlimitedto0...1023,sothewholerangeofthe
module can be used.
Forvoltages>10Vorcurrents>20mA,values>1023maybeoutput,andfor
voltages<0Vor<-10V,negativevaluesmaybeoutput.(WiththeW615itisnot
possibletooutputnegativecurrents).
This extended range does depend on the tolerances of the components, and cannot
be guaranteed.
Connection concept for voltage and current inputs
The voltage and current output signals are connected directly to the 14-pole terminal
block(O0…O5/O3and-).
The following connection diagram shows a typical wiring layout for:
● voltage outputs with the PCD2.W605 and .W625 modules or
● currentoutputsforthePCD2.W615module
Connection for 0..10 V (W605) or -10 V...+10 V (W625):
D
A
5
U
R ≥ 3 kΩ
13
4
(A2)
No external supply is needed for voltage outputs.