Mounting
30 © SICK AG • Subject to change without notice • 8021823/126P/2018-12-17
6.5 Place the distance measuring device towards the adjacent data trans-
mission photoelectric switch
When mounting with a data transmission photoelectric switch of the
ISD300, ISD400-1xxx and ISD400-6xxx series, a beam separation of at
least 100 mm must be complied with at all times. The maximum scan-
ningrangedoesnotinuencetheminimumdistance.Fordevicesofthe
ISD400-7xxx (ISD400 Pro) serie other minimum distances apply. Refer to
operating instructions “ISD400 Pro”.
Formula a≥100mm
a
S
et
E
s
c
<
<
Fig. 11: Placement of the distance measuring device to the data transmission
photoelectric switch ISD
1 Distance measuring device DL100 Pro
2 Reector
3 Data transmission photoelectric switch ISD300, ISD400-1xxx or ISD400-6xxx
a Minimum distance