8021823/126P/2018-12-17 • © SICK AG • Subject to change without notice 71
PROFINET IO-interface
10.1.3 Congureparticipants
MAC-Adresse EachPROFINETIOleddevicehasitsownMACaddress.TheMACad-
dress of the DL100 Pro PROFINET IO is written on the type label (e.g.
00:06:77:02:00:A7 → See page 18, chapter 3.1 „Type label”.
Deningdevicenameandautomati-
cally assigning IP address
Additionally,aPROFINETIOelddevicerequiresaunique,plant-specic
device name.
TheDevicenameandIPaddressaredenedasfollows:
Assume the device name assigned for the DL100 Hi PROFINET IO by the
networkengineeringtooloryoucongureauniqueplant-specicdevice
name using the network engineering tool.
• The IO controller assigns the IP address based on the device name.
Manuallydening
IP address
Manually determine the name and IP address of the distance measuring
device DL100 Pro PROFINET IO:
1. Double-click the icon of the DL100 Pro PROFINET IO in the network
engineering tool. The dialogue Properties appears.
2. Select the tab “General”.
3. Enter the device name of the DL100 Pro PROFINET IO.
4. Assign a new IP address.
10.2 Modules for cyclic data transmission
The distance measuring device is a so-called modular PROFINET IO slave.
The sent and received data structure of a modular slave is variable and
comprises several individual modules.
Themodulescanbeselecteduser-denedunderconsiderationofthe
following conditions:
• Maximum number of modules: 16
• Maximum total length of the process data: 48 input bytes and 32 output
bytes
Thedistancemeasuringdevicecanbeadjustedexiblytothedierent
controltaskswiththemodules.Thedierentmodulesaredescribedwith
theirrespectivecharacteristicsintheGSDle.