Operating instructions Chapter 11
Flexi Classic
8011509/YPP0/2015-10-26 © SICK AG • Industrial Safety Systems • Germany • All rights reserved 109
Subject to change without notice
Technical specifications
Minimum Typical Maximum
Output circuit (Y14, Y24)
Type of output
Non-isolated N/O contact, positively guided,
current-limited
Number of N/O contacts Y14/24
UE410-2RO – 1 –
UE410-4RO – 2 –
Output voltage 16 V DC 24 V DC 30 V DC
Output current
33)
– – 75 mA
Load capacity
–
– 200 nF
General data
Electrical isolation
Supply circuit-input circuit No
Supply circuit-output circuit Yes
Input circuit-output circuit Yes
Weight (without packaging)
UE410-2RO 0.16 kg
UE410-4RO 0.19 kg
Operating data
Ambient operating temperature
(UL/CSA: ambient temperature)
–25 °C – 55 °C
Storage temperature –25 °C – 70 °C
Air humidity 10 % to 95 %, non-condensing
Climatic conditions EN 61 131-2
Mechanical strength
Vibration resistance 5-150 Hz/1 G (EN 60 068-2-6)
10-500 Hz/3 G
rms
(EN 60 068-2-64)
Shock resistance
Continuous shock 10 g, 16 ms (EN 60 068-2-27)
Single shock 30 g, 11 ms (EN 60 068-2-27)
33)