Technical specifications
Minimum Typical Maximum
Output circuit (Y14, Y24)
Type of output
Non-isolated N/O contact, positively guided,
current-limited
Number of N/O contacts Y14/24
UE410-2RO 1
UE410-4RO 2
Output voltage 16 V DC 24 V DC 30 V DC
Output current
33)
75 mA
Load capacity
200 nF
General data
Electrical isolation
Supply circuit-input circuit No
Supply circuit-output circuit Yes
Input circuit-output circuit Yes
Weight (without packaging)
UE410-2RO 0.16 kg
UE410-4RO 0.19 kg
Operating data
Ambient operating temperature
(UL/CSA: ambient temperature)
–25 °C 55 °C
Storage temperature –25 °C 70 °C
Air humidity 10 % to 95 %, non-condensing
Climatic conditions EN 61 131-2
Mechanical strength
Vibration resistance 5-150 Hz/1 G (EN 60 068-2-6)
10-500 Hz/3 G
rms
(EN 60 068-2-64)
Shock resistance
Continuous shock 10 g, 16 ms (EN 60 068-2-27)
Single shock 30 g, 11 ms (EN 60 068-2-27)
33)
The total output current is limited. Maximum total current for all relay modules on Y14 and Y24 is I < 400 mA.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK Flexi Classic series and is the answer not in the manual?

SICK Flexi Classic series Specifications

General IconGeneral
BrandSICK
ModelFlexi Classic series
CategoryController
LanguageEnglish

Related product manuals