Table 11: Safety supplement C with parallel approach to the optical axis, hazardous point
pr
otection
Object resolution
H
and
Object resolution
Arm
Object resolution
Leg
Object resolution
Body
160mm 850mm Object resolution is
no
t applicable to this
application.
Object resolution is
not applicable to this
application.
Further topics
•
T
olerance zone of the device (TZ) see table 42, page 90
•
"Approach direction", page 27
4.3.12 Access protection
Access protection
T
he camera system is mounted on the passageway. In access protection applications,
the camera sensor detects the entry of an entire body.
The following fields are suitable for access protection:
•
Protective field
•
Contour detection field
The contour detection field also avoids detection gaps due to inadvertent maladjust‐
ment of the camera or due to manipulation.
Figure 21: Access protection
4.3.12.1 Protective field
In access protection, the minimum distance typically defines the position at which the
de
vice is mounted.
The protective field must be dimensioned so that a person cannot step over the protec‐
tive field. The protective field must either be 900mm high or extend at least 500mm in
the direction of movement.
PROJECT PLANNING 4
8025919/1I9E/2023-01-09 | SICK O P E R A T I N G I N S T R U C T I O N S | safeVisionary2
33