864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06 121/214
Installation
Mount the gas-insulated bar.
Bolt the pressure ring of the gas-insulated bar together with the busbar housing
using 8 bolts M8 x 20. Tightening torque: 20 Nm.
The gas-insulated bar is disassembled in reverse order: Remove the bolts at the pressure ring
of the gas-insulated bar. Remove the gas-insulated bar and bolt the cover onto
the connection housing.
Gas-insulated bar
(with integrated pressure ring
)
Pressure ring
Sealing ring
Connection housing
Fig. 134: Fixing points for the pressure ring
of the gas-insulated bar
Gas-insulated bar
Pressure ring
Connection housing
Busbar housing