Operation
162/214 Revision 06 INSTALLATION AND OPERATING INSTRUCTIONS 8DB10 864-5091.9
Emergency operation of
the DISCONNECTING
function
If the switch does not reach its end position, e.g., due to a failure of the auxiliary voltage
during disconnector operation, push the operating lever with pushed-on adapter onto
the hexagonal shaft for the DISCONNECTING function in such a way that the pin of the
hexagonal shaft fits in the inner slot of the operating adapter.
Fig. 188: Inserting the operating lever with pushed-on adapter (DISCONNECTING function)
DANGER
Danger of personal damage due to short-circuit. When switching with the emergency
operating lever with adapter, there is a risk of switching a live busbar system straight to
EARTHED position.
Turn the emergency operating lever with adapter carefully into the required end position.
When switching with the emergency operating lever with adapter, check the current
switch position continuously at the position indicator.
ATTENTION
The work-in-progress earthing contact of the disconnector in busbar system 2 is designed for
maintenance work at the three-position disconnector in busbar system 1 in de-energized
condition only.
Before switching to the work-in-progress earthing contact, always contact the regional
Siemens representative.