864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06 163/214
Operation
Push the control gate to the left.
Push the control gate to the left.
The opening for the DISCONNECTING function is free.
To switch the DISCONNECTING function of three-position disconnector to the desired end
position (CLOSED or OPEN), perform the following actions:
Turn the emergency operating lever until the position indicator changes to CLOSED or OPEN
position.
Remove the emergency operating lever again.
The control gate returns to its initial position.
The opening for the DISCONNECTING function is closed.
Fig. 189: Emergency operation of the DISCONNECTING function of the three-position disconnector
Position of emergency
operating lever
Marking of slot Position of three-position
disconnector
horizontal at the bottom CLOSED
at the top OPEN