198/214 Revision 06 INSTALLATION AND OPERATING INSTRUCTIONS 8DB10 864-5091.9
Earthing the busbar section (system 2)
1
Initial situation
2
Push the right-hand control gate to the left.
3
Switch the three-position disconnector to CLOSED position (insert the
operating lever for the DISCONNECTING function and turn 180°
clockwise).
4
Remove the operating lever for the DISCONNECTING function.
The right-hand control gate returns to its initial position.
5
Push the left-hand control gate to the right.
6
Switch the three-position disconnector to READY-TO-EARTH position
(insert the operating lever for the READY-TO-EARTH function and turn
180° clockwise).
7
Remove the operating lever for the READY-TO-EARTH function.
The left-hand control gate returns to its initial position.