864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06 91/214
Installation
Refasten the cover of the panel connection housing ④ with 11 bolt-and-washer
assemblies M8x40 (tightening torque: 20 Nm).
Fig. 98: Fastening the cover with the plug sockets
The earthing cable is either pre-assembled at the subframe, or fastened to the subframe
with cable straps.
Bolt the earthing cable to the subframe if the earthing cable is not pre-assembled.
Bolt the earthing cable ⑭ with an hexagonal bolt M8x40 (with plain washer and spring
washer) to the cover of the panel connection housing (tightening torque: 20 Nm).
Repeat the above work operations for all other panel connections in the same panel.
The panel connections are assembled.
Replacing
desiccant bags in the
circuit-breaker housings
The desiccant bags are located behind the cover of the bursting disc at the side of
the circuit-breaker housing. The cover has the inscription "Filter".
Fig. 99: Cover of bursting disc on circuit-breaker housing
Cover of bursting disc
ATTENTION
In the ambient air, the desiccant bags lose their effectiveness rapidly and cannot be used
anymore.
Use only desiccant bags whose packing is not damaged and whose humidity indicators in
the packing are blue.
➭Do not use desiccant bags if the humidity indicators are pink.
After opening the packings, mount the desiccant bags in the gas compartment within
30 minutes and close the gas compartment hermetically.