90/214 Revision 06 INSTALLATION AND OPERATING INSTRUCTIONS 8DB10 864-5091.9
Clean the sealing ring ⑥ removed from the panel connection housing, and grease it
uniformly with the supplied mounting paste (e.g. Polylub GLY 801, 0.40 kg).
Insert the sealing ring ⑥ in the groove of the cover of the panel connection housing ④ .
Fig. 95: Inserting the sealing ring
Grease the contact laminations with mounting paste Vaseline 8422 DAB 8
(order number: 8BX2091).
Fig. 96: Greasing the socket
Push the cover of panel connection housing ④ into the panel connection housing .
Fig. 97: Inserting the cover of the panel connection housing
NOTE
In other panel connection versions, the plug sockets may be arranged asymmetrically.
If the plug sockets are arranged asymmetrically, observe the mounting direction of the
cover of the panel connection housing.