System Components and Technical Data
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted 137
DC8-037-2.02, Edition 10.2017
5.5.14 PCBST0
5.5.14.1 Functions
Communication of a substation with a central station (SAT SK 1703 Slave).
Multi-point traffic slave for the transmision of SAT 1703 standard formats (external data-
base formats)
PCBST0 is substation
Traffic handling optional according to "SK 1703 Multi-point traffic (Master = PCBM00,
PCBM10, PCBMA0) or "Radio relay operation“ without routing procedure (Master =
SKSZ40, SKSZA0)
Message formats according to IEC 60870-5-1/FT1.2
Puls code modulation; byte asynchronous
Transmission rate 50 up to 19200 bps
Protection of the messages with hamming distance HA = 4
Control of the traffic handling with handshaking and message repititions upon acknowl-
edgement failure
Check of received messages
Bundle in send/receive direction
Chaining in send direction
Linear measured value adaptation
Timesetting and time synchronization of the automation unit
Multi-hierarchical configurations possible (to substations in multi-point traffic further auto-
mation units can be connected)
Note
The previously mentioned functions are described in detail in the document SICAM RTUs • Ax 1703
Common Functions SK 1703 Multi-Point Traffic GV-U.