2.2.3 Transmission Facilities
CP-8000/CP-802x supports the following transmission facilities.
Connection Transmission facility Protocol
Multi-point
traffic
Point-to-point
traffic
(serial)
CE-0700 V.23 Leased line modem
1)
PCBST0, RP5UT1, ST1ST0, TG8ST0,
UMPMT0, UMPST0
CE-0701 VFT Channel modem
1)
PCBST0, RP5UT1, ST1ST0, TG8ST0,
UMPMT0, UMPST0
CM-0819 converter RS-232/RS-485
(galvanically insulated)
103MT0, DNPST0, MODMT2, ST1ST0,
TG8ST0, UMPMT0
CM-0821 field bus interface ring (3x FO,
1x electrical)
103MT0, DNPST0, MODMT2, MODST0,
UMPMT0, UMPST0
CM-0822 field bus interface star (4x FO) 103MT0, MODMT2, MODST0, UMPMT0,
UMPST0
CM-0823 field bus interface ring (3x FO,
1x RS-485)
103MT0, MODMT2, MODST0, UMPMT0,
UMPST0
CM-0829 converter RS-232/RS-422;-485 MODST0, PCBST0, RP5UT1
CM-0847 (CM-0827) fiberoptical interface
(electrical-FO)
2)
103MT0, DNPST0, MODMT2, MODST0,
UMPMT0, UMPST0
Westermo TD-23 (analog)
3)
UMPMT0, UMPST0
SATELLINE 2ASxE PCBST0, ST1ST0, TG8ST0, UMPMT0
TP Radio WDM 8000 UMPST0
Radio digital PCBST0, ST1ST0, TG8ST0, UMPMT0,
UMPST0
Radio analog PCBST0, ST1ST0, TG8ST0, UMPMT0,
UMPST0,
Direct connection RS-232 103MT0, BPPT0, DNPMT0, DNPST0,
MODMT2, MODST0, PCBST0, RP5UT1,
ST1ST0, TG8ST0, UMPMT0, UMPST0,
Direct connection RS-485 DNPMT0, DNPST0, MODMT2, ST1ST0,
UMPMT0, UMPST0
Dial-up traffic
(serial)
Westermo TD-36 / TDW-33 (analog) DIAST0
Westermo IDW-90 (ISDN) DIAST0
Westermo GDW-11 (GSM) DIAST0
Cinterion MC52iT (dualband GSM)
4)
DIAST0
SMS
MC Technologies MC55iw Terminal SMST0
GPRS integrated GPRS modem (CP-8022) ET84
Siemens SCALANCE M874-2 ET84
Siemens MD741-1
4)
ET84
Dr. Neuhaus Tainy EMOD-V2-IO ET84
Dr. Neuhaus Tainy EMOD-L1-IO
5)
ET84
Welotech TK701G / TK704G ET84
Ethernet ET84, ET85
1)
supply 5 V via modem cable for CE-070x
2)
supply 5 V via RS-232 interface (in case of CP-8022 as of production level CC)
3)
provides RS-232 and RS-485 interface
4)
transmission of SMS possible
5)
without IPsec VPN tunnel