Preparing the Engineering
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted 245
DC8-037-2.02, Edition 10.2017
7.4 Integrated Protocol SNMP
CP-8000/CP-802x supports the protocol SNMP Agent (version 2 and version 3). For the engi-
neering of the SNMP protocol you need to get MIB files and a MIB browser.
7.4.1 Download of the MIB-Files
MIB-files can be downloaded from the website http://www.siemens.com/sicam:
Select > Home > Products, Systems & Solutions > Products for Substation Automa-
tion > Substation Control Systems and Remote Terminal Units
Click on the Downloads tab
Open SICAM AK3 | Manuals
In the result list click on SICAM RTUs SNMP MIB File in order to start the download
After the download you get the file SICAMRTUs_SNMP_MIB_V04.00.00.zip.
Save this file on the computer where the MIB-browser is installed
Open the file and start the therein contained file by means of double-click:
SICAMRTUs_SNMP_MIB_V04.00.00.exe
The MIB files are automatically stored on your computer. You find them in the subdirectory
C:/siemens/SICAMRTUS_SNMB_MIB_V04.00.00/MIB-Files.
7.4.2 Import of the MIB-Files in MIB-Browser
The import of the MIB-files into your MIB-browser must be done in the following sequence:
Import of SIEMENS-SMI.mib
Import of sicamRTUs.mib
Import of RFC1213-MIB (optional)
Import of rfc3635_mib.mib (Ethernet MIB, optional)
Import of rfc2790_mib.mib (Host Resources MIB, optional)
Import of rfc2574_mib.mib (USM MIB, optional)
Import of rfc2575_mib.mib (VACM MIB, optional)
Besides a standard MIB browser you can load the MIB files also with the control center sys-
tems SICAM 230 and 250 SCALA.