EasyManua.ls Logo

Siemens CP-8000

Siemens CP-8000
614 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
System Components and Technical Data
150 Unrestricted SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
5.7.2.3 AI-8310
5.7.2.3.1 Functions
Temperatures
t1
Connecting resistance thermometers: 2-, 3- or 4-wire technique
Settable measuring ranges
Temperature values
Input range
Pt100: -50…+350°C / -58…+662°F / (80.31…229.67 )
Pt100: -100…+700°C / -148…+1292°F / (60.25…345.13 )
Ni100: -60…+250°C / -76…+482°F / (69.5…289.2 )
Pt1000: -100…+700°C / -148…+1292°F / (602.5…3451.3 )
Resolution
Pt100: -50…+350°C 0.15°C / 0.28°F / (10 m)
Pt100: -100…+700°C 0.15°C / 0.28°F / (10 m)
Ni100: -60…+250°C 0.15°C / 0.28°F / (10 m)
Pt1000: -100…+700°C 0,15°C / 0,28°F / (100 m)
Response time
16 Hz < 1.2 s
50 Hz < 1.0 s
60 Hz < 0.9 s
Resistance values
Input range
40…400 , Resolution: 10 m
400…4000 , Resolution: 100 m
Response time
16 Hz < 1.2 s
50 Hz < 1.0 s
60 Hz < 0.9 s
Revision
Noise rejection
Calibration for 2-wire technique
Smoothing
Adaption
Temperature value (°C, °F), conversion using implemented curves
Resistance value ()
Change monitoring
Spontaneous transmission upon change

Table of Contents