Preparing the Engineering
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted 259
DC8-037-2.02, Edition 10.2017
With CP-802x, a standard patch cable and a D-sub/RJ45 adapter must be used.
Wiring for Connection CP-8000 – PC (patch cable + D-sub/RJ45 adapter)
Recommended D-sub/RJ45 adapter
RS Pro MHDA9-SMJ8-M-K (see appendix A.8.1, Recommended Third-Party Products). This
adapter provides a wired RJ45 socket and an unwired D-sub plug (female).
Wiring of the RJ45 socket: Wiring at the 9-pole D-sub plug:
Pin Wire color
1 black The assignment of the pins at the D-sub plug can be
made according to wiring diagram.
Not used wires must be isolated!
With use of the shield this must be soldered at the metal
plate of the D-sub plug.
2 yellow
3 orange
4 red
5 green
6 browne
7 grey
8 blue
Shield black
Note
If the engineering PC does not provide a serial COM port, additionally a USB/RS-
232 converter is required
(see appendix A.8.1, Recommended Third-Party Products).
CP-802x
Standard patch cable
max. 1.8 m
D-sub/RJ45
adaptor
Web browser
1
2
3
4
5
6
7
8
9
CTS
RTS
VCC
TXD
RXD
GND
DCD
DTR
1
2
3
4
5
6
7
8
DCD
RXD
TXD
DTR
GND
DSR
RTS
CTS
RI
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
X2:1
X2:2
X2:3
X2:4
X2:5
X2:6
X2:7
X2:8
shield
9-pole D-sub
female
shield
Engineering
PC
.
RJ45 socket
D-sub plug (backside)
solding point