Engineering via SICAM WEB
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted 361
DC8-037-2.02, Edition 10.2017
Category Parameter Meaning
Parameter of measured
values ACP1703
Kind_of_parameter
According NUC
Threshold value
Smoothing factor
Lower limit for transmission of measured
values
Upper limit for transmission of measured
values
Activation parameters for measured values
Interrogation-group General interrogation (group 1…16; none)
MV_CASDU1 Address of the datapoint. The complete
address consists of CASDU1, CASDU2,
IOA1, IOA2 and IOA3. CASDU1 and
CASDU2 = 255 means no spontaneous
transmission.
MV_CASDU2 Address of the datapoint. The complete
address consists of CASDU1, CASDU2,
IOA1, IOA2 and IOA3. CASDU1 and
CASDU2 = 255 means no spontaneous
transmission.
MV_IOA1 Address of the datapoint. The complete
address consists of CASDU1, CASDU2,
IOA1, IOA2 and IOA3. CASDU1 and
CASDU2 = 255 means no spontaneous
transmission.
MV_IOA2 Address of the datapoint. The complete
address consists of CASDU1, CASDU2,
IOA1, IOA2 and IOA3. CASDU1 and
CASDU2 = 255 means no spontaneous
transmission.
MV_IOA3 Address of the datapoint. The complete
address consists of CASDU1, CASDU2,
IOA1, IOA2 and IOA3. CASDU1 and
CASDU2 = 255 means no spontaneous
transmission.
MV_TI Type identification according to
IEC 60870-5-101/104
Process data command Event_(C) The data point is displayed in the event list
Text_(C) The data point is displayed with this name
(max. 13 characters)
State_TextOn_(C) The state ON for single or double point infor-
mation is displayed with this name (max.
6 characters)
State_TextOff_(C) The state OFF for single or double point
information is displayed with this name (max.
6 characters)
State_TextFlt_(C) The state faulty position for double point
information is displayed with this name (max.
6 characters)
State_TextInt_(C) The state intermediate position for double
point information is displayed with this name
(max. 6 characters)
SID-BSE Source identification basic system element
SID-ST Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254; if
automatic, the SID will be learned
SID-SSE Source identification supplementary system
element