Engineering via SICAM WEB
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted 375
DC8-037-2.02, Edition 10.2017
Processing type Parameter Meaning
Latched absolute value
Latched relative value
SVM_monitoring Power monitoring. The sensor voltage is
monitored by an own power monitoring input
(S)
transm_prompting Transmission prompting. The initiating for the
transfer of the latched count can happen
through a counter interrogation message
(group), through adjustable intervals, or
through the function diagramm. (S)
latch_prompting Latch prompting can be different to the trans-
mission prompting (S)
Value range Value range of the counter (S)
Pulse value Pulse value (S)
0.0001 bis 9999
Moduleselection_SVM_
monitoring
Switch for power monitoring handling (PM)
Standard PM (PM inputs per modules) or input
IN D17 of one BI-module as PM input for all
modules Attention: Selected module must be
a DI-module.
SW_DI – software data
point digital input
SW_DI_AR - automatic
reclosing
SW_DI_UPDATE –
update of double-point
information
Originatoraddress Allowed originator address
QOC there is no confirmation/termination for a
received command with a different QOC
SID-BSE Source identification basic system element
SID-ST Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254; if
automatic, the SID will be learned
SID-SSE Source identification supplementary system
element
SW_DI_BT – breaker
tripping
SW_DI_SOR – switching
operation running
SW_CV_SET – counter
set
SID-BSE Source identification basic system element
SID-ST Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254; if
automatic, the SID will be learned
SID-SSE Source identification supplementary system
element