Engineering via SICAM WEB
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual Unrestricted 377
DC8-037-2.02, Edition 10.2017
Processing type Parameter Meaning
Sync_Input_t_1 Within this time (in sec) the enabling over the
syncronisation input must occur on the com-
mand.
0 = no syncronisation over syncronisation
input.
Attention: Function only active if sync_t = 0
0.1 to 6553.5
1_out_of_n_t_1 Within this time (in sec) the 1 out of n enabling
must occur on the command.
0 = no 1 out of n enabling necessary.
Attention: Function only active if sync_t = 0.
0.1 to 25.5
Sw_Seq_command_seq_0 Switching sequence: output additional com-
mand before or after the command
Sw_Seq_addtl_com_0 Switching sequence: Select the additional
command
Sw_Seq_command_seq_1 Switching sequence: output additional com-
mand before or after the command
Sw_Seq_addtl_com_1 Switching sequence: Select the additional
command
RS_Mon_Source_0 Source of state information for state infor-
mation monitoring
Peripherals
Open-/closed loop control function
Both (logical OR)
RS_Mon_Source_1 Source of state information for state infor-
mation monitoring
Peripherals
Open-/closed loop control function
Both (logical OR)
SID-BSE Source identification basic system element
SID-ST Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254; if
automatic, the SID will be learned
SID-SSE Source identification supplementary system
element
QOC>8 If QOC > 8 (Qualifier of Command) is accept-
ed, so all QOC > 8 will be interpreted as
QOC = 0
ON_before_OFF Definition of the order for the wiring of double
commands/double point information.
NO: OFF is I/O with lower I/O number ON is
I/O with higher I/O number.
YES: ON is I/O with lower I/O number OFF
is I/O with higher I/O number
Regulating_command Use as regulating command (S)
NO/YES
RS_Image Parameter works only with ACP 1703 platform