Commissioning (software)
5.7 Commissioning modes
Control Units CU240S
Operating Instructions, 11/2006, A5E00766042B AA
5-45
Warning
For series commissioning, all of the communication interfaces as well as also the digital and
analog interfaces are re-initialized. This results in a brief communications failure or causes
the digital outputs to switch.
Potentially hazardous loads must be carefully secured before starting a series
commissioning.
Potentially hazardous loads can be secured as follows before starting series commissioning:
Lower the load to the floor, or
Clamp the load using the motor holding brake.
Note
Upload
Before the upload starts, the parameters will be copied from RAM to EEPROM
Manual and automatic download
With a manual download all necessary parameters excluding the fail-safe parameters (only
with CUs with fail-safe functions) are downloaded into the inverter. A manual download can
be triggered by the customer as described in the following.
With an automatic download even the fail-safe parameters are downloaded into the inverter.
An automatic download can only be performed with an MMC.
An automatic download can be performed at Start-up or by swapping an inverter component
(CU or PM), details are described in the following sections and in the chapter "Operation" of
this manual.