Commissioning (software)
5.9 Commissioning with PROFIBUS DP
Control Units CU240S
5-98 Operating Instructions, 11/2006, A5E00766042B AA
Error
value
Meaning Note Extra info
0x16 Illegal parameter address Illegal or unsupported value for
attribute, number of elements,
parameter number, subindex or a
combination of these.
0x17 Illegal format Write request: illegal or unsupported
parameter data format.
0x18 No. of values inconsistent Write request: a mismatch exists
between the number of values in the
parameter data and the number of
elements in the parameter address.
0x19 Drive object does not exist Access to a drive object which does
not exist.
0x20 Parameter text element cannot be
changed
Change access to a parameter text
element that cannot be changed.
Subindex