Communications configuring
3-110 System- and communication configuring D7-SYS - SIMADYN D
Edition 12.2003
The read, write, Get OV (detailed version) utilities and symbolic
addressing should be selected (as requester ".req") as they are
required.
Read should be selected if a receive block as client uses this
association.
Write should be selected if a transmit block uses this association
as client.
Get OV (detailed version) and symbolic addressing should be
selected if the server supports these utilities.
If SIMADYN D is the remote server, all utilities can be selected.
The maximum number of parallel tasks "Transmit" should correspond
to the number of transmit- and receive blocks, configured using CFC,
which use this communications association (as client). It should be
ensured that for a remote server, the maximum number of parallel
"Receive" tasks correspond to at least this number.
NOTE
As a result of the time characteristics of the SS5 communication module,
the "Cyclic server" communications association should not be used.
Features:
Cyclic data transfer
SIMADYN D is used exclusively server.
An association must be configured for each object, which the remote
client accesses.
The remote client establishes the connection and initiates data
transfer.
The client can access any object in SIMADYN D-OV.
Application:
Process data, with SIMADYN D as server
Cyclic server