ID/
Icons
Diagnostic Action Comment
101 Volume flow Value above warning limit. Check process con‐
ditions or align limit to normal operation. Adjust
parameter 'Upper warning limit'
102 Volume flow Value below warning limit. Check process con‐
ditions or align limit to normal operation. Adjust
parameter 'Lower warning limit'
103 Volume flow Value belove alarm limit. Check process condi‐
tions or align limit to normal operation. Adjust
parameter 'Lower alarm limit'
104 Density Value above alarm limit. Check process condi‐
tions or align limit to normal operation. Adjust
parameter 'Upper alarm limit'
105 Density Value above warning limit. Check process con‐
ditions or align limit to normal operation. Adjust
parameter 'Upper warning limit'
106 Density Value below warning limit. Check process con‐
ditions or align limit to normal operation. Adjust
parameter 'Lower warning limit'
107 Density Value below alarm limit. Check process condi‐
tions or align limit to normal operation. Adjust
parameter 'Lower alarm limit'
108 Medium temperature Value above alarm limit. Check process condi‐
tions or align limit to normal operation. Adjust
parameter 'Upper alarm limit'
109 Medium temperature Value above warning limit. Check process con‐
ditions or align limit to normal operation. Adjust
parameter 'Upper warning limit'
Diagnosing and troubleshooting
10.2 Fault codes and corrective actions
MASS 2100 & FC300 (FCT030)
Operating Instructions, 06/2017, A5E39789040-AA 195