HMI menu ID Parameter Description Default value
[unit]
Value range Access
level
2.4.5.8.16 NAMUR status signal Select one or more NAMUR sta‐
tus signals. The output is active
when one of the selected signals
occurs.
Failure
Function
check
Out of
specification
Maintenance
required
None
User
2.4.5.8.17 Polarity Set the level of an active signal. Active high level
Active high
level
Active low
level
User
2.4.5.8.18 On delay Set the time delay between
alarm condition and activating
the output. Allows to ignore tran‐
sient fault conditions
0 s
0 to 100 s
User
2.4.5.8.19 Off delay Set the time delay between re‐
setting alarm condition and de-
activating the output. Allows to
ignore transient fault conditions
0 s
0 to 100 s
User
2.4.5.9 Digital input
2.4.5.9.1 Input function Select the signal input function‐
ality.
Start dosing
Stop dosing
Reset totalizer
1
Reset totalizer
2
Reset totalizer
3
Reset all
totalizers
Zero point
adjustment
Resume
dosing
Force outputs
Freeze
process
values
User
2.4.5.9.2 CH1 forced current val‐
ue
Enter the value for the output
signal when forcing is activated.
4.00 mA 3.5 to 25 mA User
2.4.5.9.3 CH2 forced value Enter the value for the output
signal when forcing is activated.
Current
4.00 mA 3.5 to 25 mA User
Default settings
B.5 Inputs and outputs
MASS 2100 & FC300 (FCT030)
362 Operating Instructions, 06/2017, A5E39789040-AA