123/617
Building Technologies Division User Manual LMS14... CC1U7471en
5 Handling 28.01.2015
Line no.
Operating line
Default value
Min
Max
Unit
Operator unit ACS420 ACS700/ACS790
No ¦ Yes No | Yes
[4498.1]
Remote reset flame
No ¦ Yes
ParRemoteUnlockEnableFlame
No | Yes
No -
[6664.1]
AdvWindLossFlameHis
No | Yes
Adverse wind loss of flame in
history
No | Yes
Yes
[4507.1] AdvWindStartSp AdverseWind StartSpeed 1500 0 10000 U/min
[4508.1]
Adv wind target speed Adverse wind target speed 2500 0 10000 U/min
[4777.1]
PrepurgOutpLimOEM Prepurging output limit OEM
0 0 2000 kW
[4778.1]
IgnitionOutpLimOEM Ignition output limit OEM
0 0 2000 kW
[4779.1]
PartialLoad OutLimOEM Partial load output limit OEM
0 0 2000 kW
[4780.1]
HF outp OEM limit High-fire output OEM limit
0 0 2000 kW
[4781.1]
Max output limit OEM Max output limit OEM
0 0 2000 kW
[4782.1]
Min output limit OEM Min output limit OEM
0 0 2000 kW
Production
[5000.1]
SW version number SW version number - 0 65535
[4763.1]
Histo last 4 para set History of last 4 parameterizations - 0 255
[4762.1]
OnlineDD group number OnlineDD group number - 0 65535
[4689.1] CustomNumb ParaSet Customer number from parameter
set
- - - -
[3891.1]
Mains frequency Mains frequency - 0 65535
[3907.1]
Mains voltage Mains voltage - 0 65535 V
[6805.1] Operation blockage
Off ¦ On
Operation blockage
Off ¦ On
Warning!
Under the most unfavorable conditions, it may take up to 40 seconds for signal H2 from the extension modules via BSB to become refreshed in the
LMS14… This can lead to functional limitations with the DHW flow switch and to crucial situations in connection with limit functions! For such
functions, use inputs H1 and inputs H3…H7.