122/617
Building Technologies Division User Manual LMS14... CC1U7471en
5 Handling 28.01.2015
Line no.
Operating line
Default value
Min
Max
Unit
Operator unit ACS420 ACS700/ACS790
[4270.1]
Ion curr lim, change Ionization current limitation, change
of current
0,2 0 100 µA
[4398.1]
IonCurrLimPosSpdSlope Ion current limitation, positive speed
slope
10 1 10000 min
-1
[4397.1]
IonCurrLimNegSpdSlope Ion current limitation negative
speed slope
10 1 10000 min
-1
[4273.1]
Ion curr lim, filter Ion current limitation filter time 600 0 10000 s
[4337.1]
Release QAA fan param
Off ¦ On
Enable QAA fan parameters
Off ¦ On
Off -
[4352.1]
Fan PWM-Min prepurg Min manipulated variable
prepurging fan
0 0 100 %
[4612.1]
Fan PWM-Max prepurgin Max manipulated variable
prepurging fan
100 0 100 %
[4613.1]
Fan PWM-Min ignition Min manipulated variable ignition
fan
0 0 100 %
[4353.1]
Fan PWM-Max ignition Max manipulated variable ignition
fan
100 0 100 %
[4354.1]
Fan PWM-Min low-fire Min manipulated variable low-fire
fan
0 0 100 %
[4355.1]
Fan PWM-Max high-fire Max manipulated variable high-fire
fan
100 0 100 %
[4366.1]
Max speed prepurging Max speed prepurging 10000 200 10000 min
-1
[4378.1]
config respons LT/SLT
Start prevention ¦ Lockout position
Configure reaction mech LT/SLT
Start prevention ¦ Lockout position
Start prevention -
[3633.1]
Max StartAttemps TSA Repetition counter establishment of
flame
4 1 25 -
[3632.1]
Max StartAttemps oper Repetition counter loss of flame in
operation
25 1 25 -
[6086.1]
MaxStartAttempt opt 1
Inactive | Active
Maximum start attempts option 1
Inactive | Active
Inactive
[4495.1]
Remote reset SLT
No ¦ Yes
ParRemoteUnlockEnableStl
No | Yes
No -
[4496.1]
Remote reset air
No ¦ Yes
ParRemoteUnlockEnableAir
No | Yes
No -
[4497.1]
Rem res extran light ParRemoteUnlockEnableStraylignt No -