Building Technologies Division User Manual LMS14… CC1U7471en
6 The settings in detail 28.01.2015
Line no. Operating line
6204 Save parameters
No
Yes
The factory settings are overwritten with the current parameter settings, enabling the
factory settings to be configured. Using Reset to default parameters (6205), the
parameters can thus be set to the factory settings saved this way.
Warning!
Only the resettable parameters are saved!
The following table shows the resettable parameters:
Line no.
Operating line
Holidays heating circuit 1
642 Start
643 End
648 Operating level
Frost protection ¦ Reduced
Holidays heating circuit 2
652 Start
653 End
658 Operating level
Frost protection ¦ Reduced
Holidays heating circuit 3
662 Start
663 End
668 Operating level
Frost protection ¦ Reduced
Heating circuit 1
710 Comfort setpoint
712 Reduced setpoint
714 Frost protection setpoint
716 Comfort setpoint max
720 Heating curve slope
721 Heating curve displacement
726 Heating curve adaption
Off ¦ On
730 Summer/winter heating limit
732 24-hour heating limit
733 Ext’n 24-hour heating limit
No ¦ Yes
740 Flow temp setpoint min
741 Flow temp setpoint max
742 Flow temp setpoint room stat
744 Swi-on ratio room stat
746 Delay heat request
750 Room influence
760 Room temp limitation
770 Boost heating
780 Quick setback
Off ¦ To Reduced setpoint ¦ To frost Prot setpoint
790 Optimum start control max
Save parameters