6745 DHW charging alarm
Setting the monitoring time until the error message for DHW is delivered.
Error message for DHW:
Error code 126 DHW charging temperature not reached.
The flow temperature is deemed correct if the level of deviation from the setpoint is less
than 1 K. If the flow temperature setpoint is reduced by more than 4 K, the supervisory
function is deactivated until the flow temperature has cooled down to the new setpoint.
The function is also passive if – due to an ECO function or quick setback – the heating
circuit pump is deactivated.
DHW charging alarm