Building Technologies Division User Manual LMS14… CC1U7471en
6 The settings in detail 28.01.2015
Line no. Operating line
7140 Manual control
Off
On
Off
Function is deactivated.
On
Function is activated.
When manual control is activated, the relays are no longer energized and deenergized
according to the control state, but are set to a predefined manual control state in
accordance with their functions (see table below). The relay outputs are set to a state
where heat is provided, independent of their hydraulic function. The solar plant remains
Off since there is a possibility of storage tank recooling via the collector. A relay
energized with manual control can be deenergized by an electronic control thermostat
(TR) or limit thermostat (LT).
Note!
In the case of manual control, mixing valve outputs Open/Close are not controlled.
The mixing valves should be manually driven to a suitable position.
Manual control