Building Technologies Division User Manual LMS14… CC1U7471en
6 The settings in detail 28.01.2015
Line no. Operating line
7146 Deaeration function
Off
On
This parameter serves for triggering the function manually, e.g. via hotkey or menu
Maintenance/special operation. On completion of deaeration, the parameter is reset
to Off. Deaeration can also be aborted any time by setting the parameter to Off.
Off
Function is deactivated.
On
Function is activated.
Line no. Operating line
7147 Type of venting
None
Heating circuit continuous
Heating circuit cycled
DHW continuous
DHW cycled
This parameter can be used to preselect the phases of the Deaeration function (for
more detailed information, refer to chapter Deaeration function).
Once the function is started, the value serves for information purposes and shows the
phase currently handled.
None
Function as a parameter: Default, that is, the Deaeration function runs through phase 1
(heating circuit continuous), phase 2 (heating circuit cycled), phase 3 (DHW
continuous) and phase 4 (DHW cycled).
Function as an info value: Function is ended
.
Heating circuit continuous
Function as a parameter: The Deaeration function runs through phase 1 (heating circuit
continuous), phase 2 (heating circuit cycled), phase 3 (DHW continuous) and phase 4
(DHW cycled).
Function as an info value: Function is in phase 1 (heating circuit continuous).
Heating circuit cycled
Function as a parameter: The Deaeration function only runs through phase 2 (heating
circuit cycled), phase 3 (DHW continuous) and phase 4 (DHW cycled).
Function as an info value: Function is in phase 2 (heating circuit cycled).
DHW continuous
Function as a parameter: The Deaeration function only runs through phase 3 (DHW
continuous) and phase 4 (DHW cycled).
Function as an info value: Function is in phase 3 (DHW continuous).
DHW cycled
Function as a parameter: The Deaeration function runs through phase 4 (DHW cycled).
Function as an info value: Function is in phase 4 (DHW cycled).
Deaeration function
Type of venting