576/617
Building Technologies Division User Manual LMS14… CC1U7471en
6 The settings in detail 28.01.2015
Error
code
LPB
code
Description of error Priority
110 STB (SLT) lockout 9
111 Temperature limiter safety shutdown 8
117 Water pressure too high 6
117 Water pressure too high 9
118 Water pressure too low 6
118 Water pressure too low 9
119 Water pressure switch has cut out 6
119 Water pressure switch has cut out 9
121 Flow temperature heating circuit 1 not reached 6
122 Flow temperature heating circuit 2 not reached 6
125 Maximum boiler temperature exceeded 9
126 DHW charging temperature not reached 6
127 DHW legionella temperature not reached 6
128 Loss of flame during operation 6
128 Loss of flame during operation 9
129 Wrong air supply 6
129 Wrong air supply 9
130 Flue gas temperature limit exceeded 6
130 Flue gas temperature limit exceeded 9
132 Gas pressure switch safety shutdown 6
133 Safety time for establishment of flame exceeded 6
133 Safety time for establishment of flame exceeded 9
146 Configuration error sensor/controlling elements 3
151 LMS14… error, internally 3
151 LMS14… error, internally 6
151 LMS14… error, internally 9
152 Parameterization error 3
152 Parameterization error 9
153 Unit manually locked 9
160 Fan speed threshold not reached 9
162 Air pressure switch does not close 9
164 Flow/pressure switch, heating circuit error 6
164 Flow/pressure switch, heating circuit error 9
166 Air pressure switch error, does not open 9
169 Sitherm Pro system error 3
169 Sitherm Pro system error 6
169 Sitherm Pro system error 9
170 Error water pressure sensor, primary side 6
170 Error water pressure sensor, primary side 9
171 Alarm contact 1 active 6
172 Alarm contact 2 active 6
173 Alarm contact 3 active 6
174 Alarm contact 4 active 6
176 Water pressure 2 too high 6
176 Water pressure 2 too high 9
177 Water pressure 2 too low 6
177 Water pressure 2 too low 9
178 Temperature limiter heating circuit 1 3
179 Temperature limiter heating circuit 2 3
183 Unit in parameterization mode 6
183 Unit in parameterization mode 9
195 Maximum duration of the refill per charging exceeded 6
195 Maximum duration of the refill per charging exceeded 9
196 Maximum duration of the refill per week exceeded 6
196 Maximum duration of the refill per week exceeded 9