EasyManuals Logo

Siemens LMV37.4 Series User Manual

Siemens LMV37.4 Series
267 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #154 background imageLoading...
Page #154 background image
154/267
Building Technologies Basic documentation LMV37.4... CC1P7546en
17 Connection to superposed systems 17.12.2018
No. Parameter
141
Operating mode building automation
0 = off
1 = Modbus
2 = reserved
142
Setback time in the event of communication breakdown
Setting value:
0 = deactivated
1…7200 s
148
Predefined output in the event of communication breakdown with building
automation
Setting values:
For modulating operation, the setting range is as follows:
0…19.9 = burner off
20…100 = 20…100% burner output (20 = low-fire position)
For multistage operation, use the following settings:
0 = burner OFF
P1...P3 = stage 1...stage 3
Invalid = no output predefined by the building automation system in the event
of communication breakdown
Default setting: Invalid
The factory settings of the parameters are shown on the parameter list.
Note
For a detailed description of parameter 148, refer to chapter Default output via building
automation.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV37.4 Series and is the answer not in the manual?

Siemens LMV37.4 Series Specifications

General IconGeneral
BrandSiemens
ModelLMV37.4 Series
CategoryController
LanguageEnglish

Related product manuals