154/267 
Building Technologies   Basic documentation LMV37.4...  CC1P7546en 
  17 Connection to superposed systems  17.12.2018 
 
No. Parameter 
141 
Operating mode building automation  
0 = off 
1 = Modbus 
2 = reserved 
142 
Setback time in the event of communication breakdown 
 
Setting value: 
0 = deactivated 
1…7200 s 
148 
Predefined output in the event of communication breakdown with building 
automation 
 
Setting values: 
For modulating operation, the setting range is as follows: 
0…19.9 = burner off 
20…100 = 20…100% burner output (20 = low-fire position) 
 
For multistage operation, use the following settings: 
0 = burner OFF 
P1...P3 = stage 1...stage 3 
 
Invalid = no output predefined by the building automation system in the event 
of communication breakdown 
 
Default setting: Invalid 
 
The factory settings of the parameters are shown on the parameter list. 
 
 
Note 
For a detailed description of parameter 148, refer to chapter Default output via building 
automation.