  27 Parameter level  17.12.2018 
27.11.7  Cold settings for «G mod pneu», «Gp1 mod pneu» and «Gp2 mod 
pneu»   
 
 
Note 
Refer to chapter Warm settings for modulating mode («G mod», «Gp1 mod», «Gp2 mod» 
and «Lo mod»)! 
With no flame, however, no actuator travel and no automatic operation after the settings have 
been made. Here, only the air requires adjustment with 
. 
 
If run is shown in the display, the following must be observed: 
 
 
P
Vh
mi n
s%
Bild 113/0707
Identification of start for setting the curve. 
 
 
Note! 
You now have the option of pressing 
ESC
 to continue with the cold setting for 
the LMV37.4.