59/267 
Building Technologies   Basic documentation LMV37.4...  CC1P7546en 
  7 Basic unit LMV37.4  17.12.2018 
 
3.  Resetting via the PC software ACS410 
 
Refer to the documentation covering the PC software ACS410 (J7352). 
 
Error 
code 
Diagnostic 
code 
Meaning for the LMV37.4 
167  3  Manual lockout by PC software ACS410 
 
7.5.4.2.  Alarm upon start prevention 
 
If start prevention occurs, it is shown on the display of the AZL2. 
Start prevention takes place only when a heat request is delivered and when one of the 
startup criteria is not fulfilled. 
The time to elapse from start prevention to display on the AZL2 is set to a fixed value of 
5 seconds. 
 
In addition, it is possible to indicate start preventions via the alarm output. This function 
can be activated per parameter. 
 
No. Parameter 
210 
Alarm in the event of start prevention 
0 = deactivated 
1 = activated 
 
If «Alarm in the event of start prevention» is activated via the alarm relay, start 
prevention and lockout can only be distinguished via the display on the AZL2. Start 
preventions are displayed as Err:, lockouts as Loc:. 
 
 
Note 
If the reset contact X8-04 Pin 1 on the LMV37.4 is activated during a startup 
prevention, the LMV37.4 will be manually locked. 
The time from occurrence of start prevention to indication by the alarm contact equals 
the time to the display on the AZL2.