161/267 
Building Technologies   Basic documentation LMV37.4...  CC1P7546en 
  22 Operating via AZL2  17.12.2018 
22.2  Meaning of symbols on the display  
 
Parameter setting mode
Info mode
Service mode
Actuator closing
Actuator opening
Fan motor controlled
Oil preheater on
Heat request from controllers
Ignition controlled
Valve controlled
Flame present
Fault status message
Unit of current display
Bild 2e/0807
 
Figure 99: Meaning of display 
 
22.3  Brightness of display  
 
Only available with backlit LCD: 
 
The function of the backlit display is dependent on the type of LMV37.4. 
 
The brightness of the display can be adjusted from 0…100% using parameter 126. 
 
No. Parameter 
126 Display brightness 
 
22.4 Special functions  
22.4.1  Manual lockout  
 
reset
 
plus other button 
 
Press  
reset
 simultaneously with any other 
button. 
 
The LMV37.4 switches instantly to the lockout 
position, irrespective of the operating position. 
 
The display shows the fault status message. 
 
(Refer to chapter Error code list!) 
 
Display: Loc: 167 
 
The reset must be carried out as follows: 
 
reset
 
1 s 
 
When 
reset
 is pressed for 1 second, rESEt 
appears on the display.
When the button is released, the LMV37.4 is 
reset.