26/267
Building Technologies Basic documentation LMV37.4... CC1P7546en
4 Technical Data 17.12.2018
4.2 Signal cable AGV50 from AZL2 BC interface
Signal cable
Color white
Unshielded
Conductor 4 x 0.141 mm²
With RJ11 plug
Cable length
AGV50.100
AGV50.300
1 m
3 m
Location Under the burner hood (extra measures
required for SKII EN 60730-1)
4.3 Environmental conditions
Storage
DIN EN 60721-3-1
Climatic conditions Class 1K3
Mechanical conditions Class 1M2
Temperature range -20...+60 °C
Humidity <95 % r.h.
Transport
DIN EN 60721-3-2
Climatic conditions Class 2K2
Mechanical conditions Class 2M2
Temperature range -30...+60 °C
Humidity <95 % r.h.
Operation
DIN EN 60721-3-3
Climatic conditions Class 3K3
Mechanical conditions Class 3M3
Temperature range -20...+60 °C
Humidity <95 % r.h.
Installation altitude Max. 2,000 m above sea level
Caution!
Condensation, formation of ice and ingress of water are not permitted!