Building Technologies Basic documentation LMV37.4... CC1P7546en
27 Parameter level 17.12.2018
27.4 Change of OEM’s password
Parameter 042: flashes.
Press
reset
to go to level c: for password changes.
reset
Letter n: for new appears flashing.
Proceed as described in chapter Entry of password and
enter the new password (5 characters).
After entry of the last character, the password must be
confirmed by pressing
reset
.
reset
Letter r: for repeat appears flashing.
Proceed as described in chapter Entry of password and
repeat entry of the new password.
After entry of the last character, the password must be
confirmed by pressing
reset
.
7782z98/0416
SEt confirms that the new password has been saved.
Parameter 042: flashes again.
27.5 Use of parameter level
The parameters stored in the LMV37.4 can be displayed and changed on the
parameter level. Normally, all parameters have been set by the burner manufacturer –
with the exception of those for the fuel train and for fuel-air ratio control.
A description of parameter level 400, which is used for setting the fuel train and the fuel-
air ratio curve, is given in chapter Fuel-air ratio curves – settings and commissioning.
SD
AF
>1 s
Press button combination
to display
000: Int.
With , select the parameter group 100:
PArA.
With
, select the parameter group 200:
PArA.
Pressing the
reset
button takes you to
parameter 201: Burner operating mode.