7.3 Digital inputs 
7.3.1  Safety loop X3–04 pin 1 and 2 
 
Input for connection of the safety loop. When any of the series-connected contacts 
included in the loop opens, power supply to the fuel valves, the fan and the ignition 
equipment is instantly cut. 
 
The safety loop includes the following components: 
  External burner switch (ON / OFF) 
  Safety limiter / safety pressure limiter 
  External control thermostat and / or pressurestat, if required 
 Water shortage switch 
 
 
Note 
Pressure switch-max when using POC via X5-02. 
 
LMV...
Bild 273en/0916
T6.3 IEC
Safety loop
(optional pressure switch-max)
Power signal for safety loop
Protective earth (PE)
Line voltage (N)
STB
Water
shortage
Si
L
1
2
3
4
5
 
Figure 13: Safety loop X3-04 
 
For diagnostic purposes, the contacts of the components included in the safety loop and 
the burner flange contact are combined for delivering the safety loop signal. If there is 
no such signal, the system initiates safety shutdown in any event. 
 
If, with Load controller ON, there is no signal from the safety loop (start prevention), 
error code 22 is translated to text display OFF S (S = safety loop) and the numerical 
value appears in the error history. 
 
Error 
code 
Diagnostic 
code 
Meaning for the LMV37.4 
22 
OFF S 
0  Safety loop/burner flange Open 
 
For the input, a repetition counter can be parameterized. Here, it is possible to set the 
number of errors permitted until lockout occurs (refer to chapter Repetition counter). 
 
No. Parameter 
215 
Repetition limit safety loop 
       1 = no repetition 
2...15 = 1...14 number of repetitions 
     16 = constant repetition 
 
Recharging time: 
Every 24 hours 
 
 
Attention! 
In the safety loop, temporarily (<1 s) switching contacts must not be wired 
(switch or other)!