179/267 
Building Technologies   Basic documentation LMV37.4...  CC1P7546en 
  26 Service level  17.12.2018 
26 Service level  
 
The service level is used to display information about errors including the error history 
and information about the LMV37.4. 
 
 
Note 
When on the service level, you can press   or   to display the next or the previous 
parameter. 
Instead of pressing  , you can also press 
reset
 for <1 s. 
 
 
Note 
Press 
ESC
 or 
reset
 for >3 s to return to the normal display. 
 
 
P
Vh
min s %
Bild 39e/0807
Parameter
Parameter value
 
Figure 102: Service level 
Note! 
No change of values on the service level. 
 
If characters ._._ are displayed by the parameter, the 
value may consist of more than 5 digits. 
Press  
reset
 for >1 s and <3 s to display the value. 
Press  
reset
 for >3 s or 
ESC
 to return to the selection 
of the parameter number (parameter number flashes). 
 
26.1  Display of service level  
 
reset
 
P
Vh
mi n
s%
Bild 21/0707
Press 
reset
 for >3 s until SEr appears. 
When releasing 
reset
, you are on the service level. 
 
No.  Parameter 
Service level 
954  Intensity of flame 
960  Actual flow rate (fuel throughput in m³/h, l/h, ft³/h, gal/h) 
121 Manual output 
Undefined = automatic operation 
922  Incremental position of actuators 
Index 0 = fuel 
Index 1 = air 
936 Standardized speed 
161  Number of faults 
701 
● 
● 
● 
● 
● 
Error history: 701-725.01.Code 
Error history: 701-725.02.Diagnostic code 
Error history: 701-725.03.Error class 
Error history: 701-725.04.Phase 
Error history: 701-725.05.Startup counter 
Error history: 701-725.06.Output 
725  Error history: Oldest error in the history