Building Technologies Basic documentation LMV37.4... CC1P7546en
28 Parameter list LMV37.4 17.12.2018
28 Parameter list LMV37.4
Abbreviations for password level:
GA Building automation
HF Heating engineer
HF (GA) Heating engineer (building automation)
IS Info / service
OEM Manufacturer of the individual product
Par. Parameter Number of Type Edit Value range Increment Default Password level
no. elements Min. Max. setting write read
000 Internal parameters
041 Password heating engineer (HF) (4 characters) 1 Std_u16 Edit 0 65535 1 OEM OEM
042 OEM password (5 characters) 1 Std_u16 Edit 0 65535 1 OEM OEM
050 Backup / Restore via AZL2 / PC software ACS410
starting (parameterizing on 1)
Index 0 = store backup
Index 1 = start restore
Error diagnostic via negative value (refer to error
code 137)
2 Std_s8 Edit -99 50 1 0; 0 HF HF
055 Burner ID of AZL2 backup data record 1 Std_s32 Read only 0 99999999 1 0 --- HF
056 ASN summary of AZL2 backup data record 8 Std_u8 Read only 0 127 1 0 --- HF
057 Software version when setting the AZL2 backup data
record
1 Hex_16 Read only 0x100 0xFFF9 1 0 --- HF
100 General
102 Identification date 1 Datum read only 0 255 1 --- IS
103 Identification number 1 Std_u16 read only 0 65535 1 --- IS
104 Preselected parameter set: Customer code 1 Std_u8 read only 0 255 1 9 --- IS
105 Preselected parameter set: Version 1 Hex_16 read only 0 0xFFFF 1 LMV37.400Ax: V 01.06
LMV37.420Ax: V 01.07
--- IS
107 Software version 1 Hex_16 read only 0x100 0xFFF9 1 V 03.70 --- IS
108 Software variant 1 Std_u8 read only 0 255 1 LMV37.400Ax: 1
LMV37.420Ax: 2
--- IS
111 ASN summary for verification with AZL2 backup data
restore
8 Std_u8 read only 0 127 1 0 --- HF
113 Burner identification 1 Std_s32 edit 0 99999999 1 Undefined HF IS