28 Parameter list LMV37.4 17.12.2018
Par. Parameter Number of Type Edit Value range Increment Default Password level
no. elements Min. Max. setting write read
121 Manual output
Undefined = automatic mode
1 Output edit/clear 0% 100% 0,1% Undefined IS IS
123 Minimum output positioning step
Index 0 = output building automation
Index 1 = output external load controller analog
Index 2 = Power of external load controller contacts
3 Output edit 0% 100% 0,1% Index
0
1
2
Wert
0%
1%
0%
HF HF
124 Loss of flame test (TÜV test) starting (parameterized
on 1)
(switch off the fuel valves
loss of flame)
Error diagnostic via negative value (refer to error
code 150)
1 Std_s8 edit -6 1 1 0 HF HF
125 Mains frequency
0 = 50 Hz
1 = 60 Hz
1 Selection edit 0 1 1 LMV37.400Ax: 0
LMV37.420Ax: 1
HF HF
126 Display brightness 1 Std_u8 edit 0% 100% 1% LMV37.400Ax: 75%
LMV37.420Ax: 100%
HF HF
127 Timeout for menu operation 1 Std_u8 edit 10 min 120 min 1 min LMV37.400Ax: 30 min
LMV37.420Ax: 60 min
OEM HF
128 Fuel meter: Pulse valency [pulses / volume unit] 1 Std_u16 edit 0 400 0,01 0 HF HF
130 Delete display of error history
To delete the display: Set parameter to 1, then to 2
Return value 0: Job successfully completed
Return value -1: Timeout of 1_2 sequence
1 Std_s8 edit -5 2 1 0 HF HF
133
Default output at TÜV test
Invalid = TÜV test at active output
20...100 = low-fire…high-fire or stage 1 / stage 2 /
stage 3
P1...P3 = stage 1...stage 3
1 Output edit / clear 20% 100% 0,1% undefined HF HF
141 Operating mode building automation system
0 = off
1 = Modbus
2 = reserved
1 Selection edit 0 2 1 0 HF HF
142 Setback time in the event of communication
breakdown
Setting value:
0 = deactivated
1 Std_u16 edit 0 s 7200 s 1 s 120 s HF (GA) HF (GA)