207/267 
Building Technologies   Basic documentation LMV37.4...  CC1P7546en 
  27 Parameter level  17.12.2018 
 
)
Air
 
Figure 104: Setting the curvepoints 
 
Note 
Curvepoints P2 to P8 are automatically computed as a straight line between P1 and 
P9. 
 
Example 1 = gas modulating 
 
P0, P1 and P9 are set as described:  Curvepoint  Value 1 
fuel 
Value 2 
air 
P0 
30.0  22.0 
P1 
32.0  24.0 
P9 
80.0  90.0 
 
P2 through P8 have automatically been  
calculated: 
Curvepoint  Value 1 
fuel 
Value 2 
air 
P2 
38.0  32.3 
P3 
44.0  40.5 
P4 
50.0  48.8 
P5 
56.0  57 
P6 
62.0  65.3 
P7 
68.0  73.5 
P8 
74.0  81.8