Building Technologies Basic documentation LMV37.4... CC1P7546en
4 Technical Data 17.12.2018
Threshold values when flame is supervised by an ionization probe:
Start prevention (extraneous light) Intensity of flame (parameter 954) 18%
Operation Intensity of flame (parameter 954) >24%
0
10
20
30
40
50
60
70
80
90
100
0246810121416
Fla
m
e intensity in
%
Ionization current in µA
Ionization input
Bild 442en/0916
Figure 5: Ionization input at AC 120 V / AC 230 V
Ionization probe
LMV...
M
C
ION
X10-05/2
X10-05/1
Legend
C Electrolytic capacitor 100...470 µF; DC 10...25 V
ION Ionization probe
M Microammeter Ri max. 5000
Figure 6: Measuring circuit for ionization probe
Measuring circuit for
detector current
measurement