Building Technologies Basic documentation LMV37.4... CC1P7546en
7 Basic unit LMV37.4 17.12.2018
Functions with adjustable repetition counter
No. Parameter
194 Repetition limit no flame at the end of safety time
1 = no repetition
2...4 = 1...3 repetitions
Recharging time:
Entering into operation
195 Repetition limit heavy oil direct start
1 = no repetition
2...15 = 1...14 number of repetitions
16 = constant repetition
Recharging time:
End of Shutdown phase
196 Repetition limit air pressure failure
1 = no repetition
2 = 1 repetition
3 = 2 repetitions
Recharging time:
End of Shutdown phase / 24 hours continuous operation
199
Repetitions limit value - actuators
1 = no repetition
2 = 1 repetition
3 = 2 repetitions
215
Repetition limit safety loop
1 = no repetition
2...15 = 1...14 number of repetitions
16 = constant repetition
Recharging time:
Every 24 hours
223
Repetition limit pressure switch-min gas
1 = no repetition
2...15 = 1...14 number of repetitions
16 = constant repetition
Recharging time:
After the Operation phase
240
280
Repetition limit value loss of flame
1 = no repetition
2 = 1 repetition
Recharging time:
After the Operation phase