What to do if Siemens DC Drives motor fails to start after the ON command?
- GGary EvansAug 23, 2025If a Siemens DC drive motor doesn't start after giving the ON command, ensure that a valid ON signal is present. Also, verify that parameter P0700 is set to 2 for digital input control or to 1 for BOP control. Finally, check that the setpoint is present (0 to 10V on Terminal 3) or has been entered into the correct parameter, depending on the setpoint source (P1000). 