I/O device digital inputs/digital outputs
9.1 I/O device digital inputs
ET 200eco PN
120 Operating Instructions, 08/2016, A5E01250250-AJ
• At signal "1"
Typ. 7 mA
• At "0" to "1"
Typ. 3 ms
• At "1" to "0"
Typ. 3 ms
According to IEC 61131, Type 3
Connection of 2-wire proximity switches
• Permitted quiescent current
Max. 1.5 mA
Parameter overview digital inputs
Parameters for 8 DI DC 24V 4×M12 (6ES7141-6BF00-0AB0) and for 8 DI DC 24V 8×M12 (6ES7141-
6BG00-0AB0)
Group diagnostics
• Disable
• Enable
Disable Device
Diagnostics: Missing 1L+
• Disable
• Enable
Disable Device
Diagnostics: Wire break at inputs 0 to 7
(channels 0 to 7)
• Disable
• Enable
Disable Channel
Diagnostics: Short-circuit to M, inputs
0,4/1,5/2,6/3,7 (channels 0,4/1,5/2,6/3,7)
• Disable
• Enable
Disable Channel group
Parameters for 16 DI DC 24V 8×M12 (6ES7141-6BH00-0AB0)
Group diagnostics
• Disable
• Enable
Disable Device
Diagnostics: Missing 1L+
• Disable
• Enable
Disable Device
Diagnostics: Wire break at inputs 0 to 15
(channels 0 to 15)
• Disable
• Enable
Disable Channel
Diagnostics: Short-circuit to M, inputs
0,8/1,9/2,10/3,11/4,12/5,13/6,14/7,15
(channels
0,8/1,9/2,10/3,11/4,12/5,13/6,14/7,15)
• Disable
• Enable
Disable Channel group