IO-Link Master (6ES7148-6JD00-0AB0)
Article number
6ES7148-6JD00-0AB0
The IO-Link Master 4 IO-L 4×M12 has the following technical specifications:
● IO-Link Master according to IO-Link specification V1.1
● Dimensions 30 x 200 mm
● 4 IO-Link ports (Port Class B)
● IO-Link ports can be used optionally as:
– 4 IO-Link devices (Port Class A oder Class B) with variable address area up to 32 byte
inputs/32 byte outputs per port
– 4 standard actuators/encoders (SIO mode)
● Data transfer rates COM1 (4.8 kBaud), COM2 (38.4 kBaud), COM3 (230.4 kBaud)
● Configurable diagnostics can be set per port (in IO-Link mode)
● Parameterization of IO-Link parameters per S7-PCT V3.4 and higher
● Autostart (without S7-PCT)
● Hardware interrupts (in IO-Link mode)
The module supports the following functions:
● Master backup
● Firmware update
● Media redundancy
● Identification and maintenance data I&M0 to I&M3
Table 11- 4 Pin assignment of sockets X1 to X4 for IO-Link master
View of socket
(front view)
S
(derived from 1L+ non-switched)
24 V actuator supply 2U
A
(derived from 2L+ switched)
3 Sensor supply ground 1M
5 Actuator supply ground 2M