Wiring
3.6 Pin assignment of connectors
ET 200eco PN
Operating Instructions, 08/2016, A5E01250250-AJ
49
3.6.6
Pin assignment for IO-Link Masters
IO-Link Master 4 IO-L + 8 DI + 4 DO DC 24V/1,3A 8×M12 (6ES7148-6JA00-0AB0)
The following tables contain the pin assignments for the IO-Link Master
4 IO-L + 8 DI + 4 DO DC 24V/1,3A 8×M12.
Table 3- 12 Pin assignment for IO-Link Master and digital inputs
Pin
Assignment of X1 to X4
View of the cable connector
(wiring side)
1 24 V sensor supply 1U
S
(derived from 1L+ non-switched)
2 Input signal DI
0
: Connector X1
Input signal DI
1
: Connector X2
Input signal DI
2
: Connector X3
Input signal DI
3
: Connector X4
3
Sensor supply ground 1M
4 IO-Link Master
Port 1 (C/Q): Connector X1
Port 2 (C/Q): Connector X2
Port 3 (C/Q): Connector X3
Port 4 (C/Q): Connector X4
5 Not used
Table 3- 13 Pin assignment for digital inputs
Pin
Assignment of X5 and X6
View of the cable connector
(wiring side)
1 24 V sensor supply 1U
S
(derived from 1L+ non-switched)
2 Input signal DI
5
: Connector X5
Input signal DI
7
: Connector X6
3
Sensor supply ground 1M
4 Input signal DI
4
: Connector X5
Input signal DI
6
: Connector X6
5 Functional earth FE