I/O device digital inputs/digital outputs
9.2 I/O device digital outputs
ET 200eco PN
146 Operating Instructions, 08/2016, A5E01250250-AJ
Parameter overview digital outputs
Parameters for
● 8 DO DC 24V/1,3A 4×M12 (6ES7142-6BF00-0AB0)
● 8 DO DC 24V/1,3A 8×M12 (6ES7142-6BG00-0AB0)
● 8 DO DC 24V/2,0A 8×M12 (6ES7142-6BR00-0AB0)
Group diagnostics
• Disable
• Enable
Disable Device
Diagnostics: Missing 1L+ or 2L+
• Disable
• Enable
Disable Channel group
Response to CPU/Master STOP
• Shut down
• Retain last value
Shut down Device
Diagnostics: Wire break at outputs 0 to 7
(channels 0 to 7)
• Disable
• Enable
Disable Channel
Diagnostics: Short circuit to M,
outputs 0 to 7 (channels 0 to 7)
• Disable
• Enable
Disable Channel
Parameters for 8 DO DC 24V/0,5A 4×M12 (6ES7142-6BF50-0AB0)
Group diagnostics
• Disable
• Enable
Disable Device
Diagnostics: Missing 2L+
• Disable
• Enable
Disable Device
Response to CPU/Master STOP
• Shut down
• Retain last value
Shut down Device
Diagnostics: Wire break at outputs 0 to 7
(channels 0 to 7)
• Disable
• Enable
Disable Channel
Diagnostics: Short circuit to M,
outputs 0 to 7 (channels 0 to 7)
• Disable
• Enable
Disable Channel