ET 200eco PN
Operating Instructions, 08/2016, A5E01250250-AJ
154
I/O device analog input/analog output
I/O device analog input
10.1.1
I/O device 8 AI 4 U/I + 4 RTD/TC 8xM12
Article number
6ES7144-6KD00-0AB0
● 4 inputs for voltage and current measurement (2-wire and 4-wire transducers)
● 4 inputs for resistance (2-/3-/4-wire transducer), thermal resistor (2-/3-/4-conductor
connection system), thermocouple or ±80 mV
● Input ranges:
– ±10 V, resolution 15 bits + sign
– ±80 mV, resolution 15 bps + sign
– 0 to 10 V, resolution 15 bits
– 1 to 5 V, resolution 15 bits
– ±20 mA, resolution 15 bits + sign
– 0 to 20 mA, resolution 15 bps + sign
– 4 to 20 mA, resolution 15 bits
– 150, 300, 600, 3000 Ω, resolution 15 bps
– Ni100, Ni1000, Ni120, Ni200, Ni500, Pt100, Pt1000, Pt200, Pt500, resolution 15 bps +
sign
– E, J, K, N, resolution 15 bps + sign
● Dimensions 60 x 175 mm
● Diagnostics
– "Missing L1+" supply voltage
– "Sensor supply short-circuit"
– "Wire break"
– "Underflow"
– "Overflow"
● Permitted common-mode voltage AC 10V
PP
● Prioritized startup
● Media redundancy
Note
During startup
As long as no parameters are assigned for the I/O device, the I/O device supplies the
process values 0x7FFF.